ZXr-A / ZXr-P Repeaters MORLEY-IAS
Operation & Installation Manual Document No. 996-144, Revision: 02, Page 11 of 16
4 Operation and Controls
The ZXr-A / ZXr-P Repeaters are equipped with a backlit 2x40 Liquid Crystal Display and LED Indicators
to show the status of the Fire Alarm Control Panel (FACP) and the installation.
In addition, the ZXr-A is equipped with a key operated switch and five CONTROL keys and a TEST key.
The operation of the Repeater is as follows:
4.1 Liquid Crystal Display
The operation of the liquid crystal display is identical to the display on the FACP.
Under normal conditions it will simply show the time and date, together with a message to show that the
detectors are working normally. The backlight is normally off. It will turn on for 30 seconds whenever a key
is pressed. It will always turn on during a fire alarm condition.
If any fault or fire alarm conditions occur, these will be displayed on the display. If several faults or fires
have occurred, then these will be scrolled on the display.
Refer to the FACP Manuals for information on the messages that are displayed.
4.2 LED Indicators
Power
Fault
A
cce
p
ted
Disablement
Silenced
FIRE
Comms. Fail
The LED indicators (except DC Power) will be
illuminated in response to signals from the
FACP.
The LED Indicators are a sub-set of the
indicators on the FACP. The following table
indicates the function of each LED indicator.
Refer to the FACP Manuals for further
information on the function and operation of each
LED indicator and on the operation of the
system.
Indicator Colour Function
FIRE Red The panel has detected a fire alarm condition,
or the ‘Sound Alarms’ key has been pressed.
Fault Yellow The panel has detected a fault.
Accepted Yellow A fault or fire alarm has been acknowledged
and the internal buzzer silenced.
[After pressing the ‘Mute Buzzer’ or ‘Accept’
keys at either the FACP or the Repeater].
Disablement Yellow Part of the system, either input or an output,
has been disabled.
Silenced Yellow The sounder outputs have been silenced.
[After pressing the ‘Silence / Resound’ key at
either the FACP or the Repeater].
Comms. Fail Yellow The repeater has lost contact /
communications with the FACP and is unable
to update its LCD and LED indicators. The
control buttons on the ZXr-A will not function
during this condition.
Power Green ON: Indicates DC Power is present.
Table 2 - LED Functions