Specification
Part Numbers
722-001-301 ZX1Se Fire Alarm Control Panel
795-066-100 Apollo XP95 & Discovery Loop Driver Card (460mA)
795-058-105 Hochiki ESP Loop Driver Card (460mA)
795-044-001 Nittan Loop Driver Card
795-068-100 System Sensor Loop Driver Card (460mA)
795-072-100 Morley-IAS Loop Driver Card (460mA)
795-005 RS232 Communication Card
795-004-001 RS485 Communication Card
797-061 ZX1Se Bezel Kit
797-063 ZX1Se Glass Door Kit
795-082 Engineer’s Software Programming Kit including Fire 6
795-080 Programming interface lead
795-081-001 Fire 6 Enhanced Feature Set Software Key
795-014 4 way programmable relay module, pcb only
795-015 4 way programmable sounder module, pcb only
795-029 8 way programmable input module, pcb only
795-038-001 Hi-485 communication module, pcb only
795-065 40 way programmable mimic interface module, pcb only
709-601-001 ZXr-A Active Repeater. LCD, System Status
indicators and user controls for Silence, Reset, Mute
and Evacuate all activated by a key switch.
709-701-001 ZXr-P Passive Repeater. LCD and system status
indicators
020-600-002 Bezel Kit for ZXr series repeaters
795-060-002 External remote printer module
797-056 External Printer Bezel Kit
795-057 MODBUS interface unit
795-067-001 Paging system interface module. Suitable for SCOPE,
ASCOM/TELENOVA
LED type general panel status indicators
FIRE, FAULT, ACKNOWLEDGED, DISABLEMENT, TEST,
SOUNDER FAULT, DELAYED MODE, RELAYS DISABLED,
EARTH FAULT, SYSTEM /CPU FAULT, SOUNDERS DISABLED,
ALARMS SILENCED, SUPPLY FAULT, POWER.
LED type zone Indicators (for 20 zones)
FIRE, FAULT/TEST/DISABLED
Display
4x40-character LCD alphanumeric display with back-light.
Serial Interface
2 serial ports with connections for optional RS485 or RS232
plug-in communication cards.
Networking
Maximum 99 panels can be networked using a Master
Network and connected Sub-Networks.
Fire System Compatibility
Morley-IAS is fully committed to offering practical solutions and supporting products that enhance your buildings control systems.
Other Supporting Products Include
Morley-IAS Intelligent Public Address and Voice Alarm Equipment
Morley-IAS Visualeyez range of Alarm Management Graphical Interface Systems
Morley-IAS Dimension Analogue Addressable Panels
Morley-IAS Horizon Conventional Panels
Morley-IAS Extinguishing Panels
For further details on these or any other Morley-IAS product please contact your local distribution point, Morley-IAS Regional Sales Manager or
via our contact details.
Morley-IAS by Honeywell a real choice for fire detection solutions, committed to supporting our device partners.
Charles Avenue
Burgess Hill
West Sussex
RH15 9UF UK
T: +44 (0) 1444 23 55 56
F: +44 (0) 1444 25 44 10
www.morley-ias.co.uk
Operating Voltage 230V 50Hz AC
(+10%, -15% voltage tolerance)
Max. PSU Rating
2.5A total, comprising: Battery Charger: 0.5 Amp
Internal & External Loads
General System Load: 1.8A @ 24V nominal
Max Loop Load: 460mA
Standby Batteries 24V sealed lead acid batteries
Minimum Capacity: 2x 12V 7Ah
Maximum Capacity: 2x 12V 12Ah
Dimensions (mm) 400 x 400 x 135 (H x W x D)
Weight 10 kg without batteries
Environmental Operating Limits
Temperature: 0°C to +40°C
Humidity: 85% non-condensing (maximum)
Construction Sheet steel painted, sealed to IP30
Cable Entry 14 x 20mm knock-outs in top of cabinet
2 x 20mm knock-outs in bottom of cabinet
Loop Capacity 1 Loop 460mA Maximum
Apollo, Nittan and Hochiki Protocols:
Max. 126 devices (detectors and modules) per loop
Morley-IAS and System Sensor Protocols:
Max. 99 sensor and 99 module addresses per loop
Note: Mulitiple sensor protocols cannot be used in the panel simultaneously.
Zones Up to 20 zone with individual LED indicators.
Internal Sounder Intermittent buzzer (fault condition) High-
pitched continuous buzzer (fire condition)
External Outputs
Sounder Outputs 2 programmable outputs. Open and short
circuit monitoring. 1A maximum per output.
Auxiliary Relays 1 fault and 1 fire relay voltage free, changeover
outputs Contacts rated at 24V AC/DC, 1A, 0.6 PF maximum.
User Controls
SOUND ALARMS, SILENCE/ RESOUND, MUTE BUZZER,
ACCEPT, SYSTEM RESET
Programming Controls
Alphanumeric multi-level keypad with 15 keys and 5 control
keys: YES, NO, CHANGE, ENTER and SHIFT